Phân phối Lenze Automation Lenze system bus

Lenze system bus

Lenze system bus

LenS16

Direct data exchange between drive controllers for synchronisation and basic communication with sensors, actuators or operating and display units without the need for an intermediate open-loop control. These functions can be provided by the following fieldbus function modules supporting parts of the CANopen communication profile in accordance with DS301. In addition, the communication to a superimposed control system is possible.

Type System bus function module
CAN
 
System bus function module
CAN
 
Order designation E82ZAFCC E82ZAFCC001
Topology Line with terminating resistors Line with terminating resistors
Max. no. of devices 63 63
Max. size  Depends on the baud rate used:
1 km at 50 kBit/s;
80 m at 500 kBit/s
 Depends on the baud rate used:
1 km at 50 kBit/s;
80 m at 500 kBit/s
Transmission medium  Shielded twisted pair  Shielded twisted pair
Transmission rate 20 - 500 kBit/s 20 - 500 kBit/s
Process data size  2 PDO channels  2 PDO channels
Suitable for use with 8200 vector, DrivePLC 8200 vector, 8200 motec, Drive PLC, starttec
Special features Terminal for activating the controller inhibit Coated version of the E82ZAFCC module

 

Type System bus function module
CAN PT
 
Order designation E82ZAFCC010
Topology Line with terminating resistors
Max. no. of devices 63
Max. size Depends on the baud rate used:
1 km at 50 kBit/s;
80 m at 500 kBit/s
Transmission medium  Shielded twisted pair
Transmission rate 20 - 500 kBit/s
Process data size  2 PDO channels
Suitable for use with 8200 vector, DrivePLC
Special features As the E82ZAFCC but with plug-in terminals

 

Type System bus function module
CAN-I/O RS PT
 
Order designation E82ZAFCC100
Topology Line with terminating resistors
Max. no. of devices 63
Max. size Depends on the baud rate used: 3,93 km at 20 kBit/s;
9 m at 1 MBit/s
Transmission medium  Shielded twisted pair
Transmission rate 20 - 1000 kBit/s
Process data size  2 PDO channels
Suitable for use with 8200 vector
Special features Terminal for activating the controller inhibit and for the external power supply to the module and the 8200 vector control card; DIP switch for setting the address and the baud rate

 

Type System bus function module
CAN-I/O
 
System bus function module
CAN-I/O
Order designation E82ZAFCC200 E82ZAFCC201
Topology Line with terminating resistors Line with terminating resistors
Max. no. of devices 63 63
Max. size  Depends on the baud rate used: 3,91 km at 20 kBit/s;
80 m at 500 kBit/s
 Depends on the baud rate used:
1 km at 50 kBit/s;
80 m at 500 kBit/s
Transmission medium  Shielded twisted pair  Shielded twisted pair
Transmission rate 20 - 500 kBit/s 20 - 500 kBit/s
Process data size  2 PDO channels  2 PDO channels
Suitable for use with 8200 vector 8200 vector, 8200 motec
Special features Terminal for activating the controller inhibit and 2 freely configurable dig. inputs; DIP switch for setting the address and the baud rate Coated version of the module E82ZAFCC200

 

Type System bus function module
CAN-I/O PT
 
Order designation E82ZAFCC210
Topology Line with terminating resistors
Max. no. of devices 63
Max. size  Depends on the baud rate used: 3,91 km at 20 kBit/s;
80 m at 500 kBit/s
Transmission medium  Shielded twisted pair
Transmission rate 20 - 500 kBit/s
Process data size  2 PDO channels
Suitable for use with 8200 vector
Special features As the E82ZAFCC200 but with plug-in terminals